SF6 Gas Insulated Sectionalizer
PRODUCTS

APPLICATION
SF6 gas insulated sectionalizer is designed for a self-contained circuit-opening device used in junction with
source-side protective devices such as reclosers and circuit breakers.
It automatically isolate faulted sections of electrical distribution systems.
SF6 gas insulated sectionalizer is designed for a self-contained circuit-opening device used in junction with source-side protective devices such as reclosers and circuit breakers.
It automatically isolate faulted sections of electrical distribution systems.
The sectionalizer has distinct application advantages
- It can be applied between two protective devices having operating curves, which are close together.
This is a vital feature in a location where an additional step in coordination is not practical or possible. - It can be used on close-in taps where fault current is highly frequent, coordinating with fuses.
- It has fault close and latch capability for any fault-closing operations.
CHARACTERISTIC
- Easy maintenance and reliable operation
- Compact design and easy installation
- Safety devices (low pressure interlocking, pressure relief, and safety locks)
Specifications shown below can be adjusted, without notice, to improve its performance.
The product can be customized to fit customer’s requirements.
Specifications shown below can be adjusted, without notice, to improve its performance.
The product can be customized to
fit customer’s requirements.
SPECIFICATION
Specification | Unit | Value |
---|---|---|
Rated voltage | kV | 12 (max.15) / 24 (max.27) / 36 (max.38) |
Rated current | A | 400 / 630 |
Power frequency withstand voltage | kV | 50 / 60 / 70 |
Impulse withstand voltage | kV | 125 / 150 / 170 |
Rated short time withstand current | kA, RMS | 10 / 12.5 / 16 |
Rated short circuit making current | kA, peak | 26 / 32.5 / 40 |
Minimum running current | A (Phase) | 50, 70, 100, 140, 200, 300, 400A (Block) |
A (Ground) | 25, 35, 50, 70, 100, 150, 200A (By Pass) | |
Rated short circuit breaking current | A | 900 |
Applied Standard | – | IEEE Std 37.63 / IEC60265-1, KEPCO std. |