SF6 Gas Insulated Vacuum Recloser
PRODUCTS

APPLICATION
SF6 gas insulated vacuum recloser is designed to use on overhead distribution lines as well as distribution
substation applications.
The magnetic actuator provides highly efficient and reliable performance while consuming very little energy.
It has a microprocessor based controller that provides the protection, data logging and communication functions.
SF6 gas insulated vacuum recloser is designed to use on overhead distribution lines as well as distribution substation applications.
The magnetic actuator provides highly efficient and reliable performance while consuming very little energy.
It has a microprocessor based controller that provides the protection, data logging and communication functions.
CHARACTERISTIC
- Fault detection & protection.
- Self-diagnosis control & status monitoring
- Adjusting T-C curve
- Sequence operational test (trip, reclosing, resetting)
- Recording (events, fault current waveforms, data logging)
Specifications shown below can be adjusted, without notice, to improve its performance.
The product can be customized to fit customer’s requirements.
Specifications shown below can be adjusted, without notice, to improve its performance.
The product can be customized to
fit customer’s requirements.
SPECIFICATION
Specification | Unit | Value |
---|---|---|
Rated voltage | kV | 12 (max.15) / 24 (max.27) / 36 (max.38) |
Rated current | A | 400 / 630 / 800 |
Rated short circuit making current | kA, peak | 32.5 / 40 |
Minimum running current | A (Phase) | 10–1600A (step: 1A) |
A (Ground) | 2–1600A (step: 1A) | |
Rated short circuit breaking current | kA | 12.5 / 16 |
Power frequency withstand voltage | kV | 50 / 60 / 70 |
Impulse withstand voltage | kV | 125 / 150 / 170 (200) |
Manual / Automatic | – | Magnetic Actuator |
Mechanical endurance | times | 5,000 / 10,000 |
Weight | kg | 160 / 160 / 300 |
Applied Standard | – | ANSI C37.60, IEC62271-111, KEPCO std. |